Case review: pitting on 316L coastal curtain-wall mullions (anonymised)
316L coastal curtain-wall mullions showed pitting after two years. The root cause was free-iron contamination plus crevices plus high chlorides; remediation combined pickling/passivation, drainage and regular cleaning.
An anonymised case review for reference in similar projects (no client-identifying information).
Background: stainless 316L mullions on a coastal building showed rust spots and pitting after about two years.
Investigation:
1) On site: rust concentrated at mullion bottoms and gasket contact areas — crevices and dirt traps.
2) Testing: positive blue-dot test, indicating free iron contamination on the surface.
3) Analysis: cutting and welding during installation were not followed by thorough pickling and passivation; combined with high coastal chlorides and crevice geometry, pitting and crevice corrosion developed.
Root cause: free-iron contamination + trapped water in crevices + high-chloride environment. The material itself was not the main issue — 316L is a reasonable choice for this environment.
Remediation:
• Full pickling and passivation to remove free iron and scale.
• Detail redesign: improve drainage, avoid water under gaskets, reduce crevices.
• Regular cleaning, especially salt deposits in coastal areas.
• Grind and re-passivate pitted areas; replace severely affected parts.
Lesson: in coastal service, choosing the right grade is only the first step — surface treatment and drainage determine service life. Require pickling/passivation records and blue-dot testing at acceptance.